Description
1. The use of voltage method for one-time wiring test can simultaneously complete CT excitation characteristics, ratio, polarity, and secondary winding DC resistance testing, improving work efficiency;
2. When measuring the ratio and polarity of current transformers, there is no need to short-circuit other secondary windings, which improves work efficiency;
3. Apply AC current to the CT secondary circuit for load measurement of the secondary circuit;
4. Isolate the output voltage from the input power supply to ensure equipment and personal safety;
5. The output voltage frequency of the experiment is independent of the input power frequency, and the output voltage frequency can be selected as 50Hz or 60Hz;
6. It can be boosted to 2000V without the need for an external booster;
7. Fully automated testing does not require manual adjustment;
8. Automatically draw 5% and 10% error curves;
9. It has the function of current boost and hold, used for testing the transformation ratio, polarity, and secondary circuit inspection of current transformers;
10. Equipped with boost holding function, used for secondary AC withstand voltage test;
11. Large screen transparent LCD display, which can display clearly both indoors and outdoors;
12. The ultra large capacity storage can store test data for 20000 sets of windings;
13. Use a USB flash drive to transfer data files and upgrade software;
14. The inflection point voltage shall be calculated according to the IEC60044-1 standard;
15. Switch between Simplified Chinese and English operation interfaces at will.
Power supply | 198 to 264V AC 47 to 63Hz |
Voltage output | 0 - 200V AC /10A |
0 - 900V AC /2A | |
0 - 2000V AC /1A | |
Current output | 0 - 200A AC /10V |
Output frequency | 50Hz or 60Hz |
Current measurement | Error: ± (0.5% rdg+2dig) Resolution:0.1mA |
Voltage measurement | Error: ± (0.5% rdg+2dig) Resolution:10mV |
Ratio measurement | Error: ±0.5% |
Burden of secondary circuit | 0~1000VA,resolution:0.001VA |
Measurement range of winding resistance | 0.1 - 100Ω resolution:1mΩ |
Accuracy of resistance measurement | ± (0.5%rdg+3dig) |
Dimensions | 492 × 392 × 218 mm |
Weight | 20kg |
Environment | Temperature: -10~50°C Humidity ≤90%RH Non-condensing |